  1. Spanky

    Elk M1RF2G (GE) wireless false alarms

    Most false alarms I have experienced are due to faulty tampers on the transmitters. One company in Chicago had tampers falling off some transmitters that were finally recalled. You can disable the tamper switch on burglar transmitters by defining the hardware hookup type on the M1 zone...
  2. Spanky

    Elk Navigator Menu Issue

    Thanks for the input. We will add it to the To-Do List.
  3. Spanky

    Elk M1G and Radio Ra 2

    You can send lighting commands with Rules from the M1, but not text strings directly to Radio Ra2.
  4. Spanky

    Procedure for adding keypad #2

    All the keypads come from the factory set to address 1. You must make sure each keypad has a separate address or you will get data bus conflicts.
  5. Spanky

    Elk M1G and Radio Ra 2

    Radio RA2 is operational and working great. It should be released soon.
  6. Spanky

    Elk Time or Daylight savings mess up

    It is fixed in the next M1 software update.
  7. Spanky

    "Level 8" Message

    When the M1 announces "Level 2 to 8", you are in the walk test or wireless transmitter enrollment mode. The "Level X" announcement is how many packets the RF receiver has decoded which indicates the relative signal strength of the RF transmitter.
  8. Spanky

    Few newbie questions on Elk M1 install

    It may be easier to program the M1 from Elkrp either via a direct connect or using the Ethernet interface. The M1 can power directly what you have listed.
  9. Spanky

    Email not working, tried 5 different pop 3 accounts/ports... what gives?

    The M1XEP requires an email service that does not use encryption. The operating system in the M1XEP does not support sign on encryption.
  10. Spanky

    Elk M1KPNAV Question

    I have sent your comments and observations to the grand puba of the Navigator. Thanks
  11. Spanky

    Elk M1XSP behavior - misses first command from M1

    I think you found an issue in the M1XSP. We have fixed the software and it will be available in the next release. In the mean time you can code around the issue by breaking the Rules down into separate Rules and putting a few seconds between the Rules. Thanks for the heads up.
  12. Spanky

    Elk M1XIN enrollment problem

    Lakehouse, Check the standard things: 1. With the power off, measure data A to data B with an ohm meter and see if it is 65 ohms +-10 ohms. Make sure you have two and only two termination jumpers at the extreme ends of the data bus wire run. 2. Make sure M1 data A connects to data A and M1...
  13. Spanky

    How does an M1 associate serial interfaces to thermostats?

    Each thermostat must have a unique address because the M1 addresses them globally.
  14. Spanky

    Elk M1 Battery Not Charging

    If the M1 is starting with a transformer connected when you turn on the power switch, it is looking more like the power supply on the M1. If the transformer was not working, the M1 will not start with a battery connected until the startup pads are shorted on the PCB. A working transformer will...
  15. Spanky

    Elk monitored temperature sensor 400 - 800 deg?

    Since the stove radiates heat, a standard sensor placed some distance away may be an easier solution than trying to mount the sensor directly on the stove.
  16. Spanky

    Can an ELK M1 be programed to give a daily timed output based on a F button

    You can pretty much design a full blown sprinkler controller with the M1. You can add water sensors or do pulse counting from a rain guage pulser so that it does not sprinkle when it has rained recently. Of course you can have the security system operational at the same time.
  17. Spanky

    Delayed response elk navigator

    I checked the response time on a Navigator here and it responds as quick as a regular keypad. We will see what is going on. Sorry for the issue.
  18. Spanky

    Need assistance w/ELK M1 rules

    Do not set F4 for Momentary Disarm. That will disarm the entire control. Set it for "Non Alarm" setting 16. That way only the Rule Engine will look at the button and it will not affect anything else.
  19. Spanky

    Elk M1 Battery Not Charging

    With the battery disconnected, measure the voltage on the aux power terminals. It should read about 13.8 volts DC. The M1 should work with no battery connected. Measure the AC voltage at the transformer input terminals on the M1 board. It should read about 19 Volts AC.
  20. Spanky

    Delayed response elk navigator

    If you are getting long delays on keypad responses, it indicates a data bus issue. Verify that your keypads are on separate addresses. Re-enroll the devices. Make sure you are series wiring the devices as shown in the installation manual and you have a terminating resistor at each end of the...